OEM Famous CT/VT compartment Quotes –Suspension type Polymeric Insulator – HolleyDetail:
Specifications
| Products Type |
| SUSPENSION TYPE POLYMERIC INSULATOR 13.8 kV | SUSPENSION TYPE POLYMERIC INSULATOR 22.9 kV |
| Features | Unit | Value | Value |
1 | Operating voltage (Phase – Phase) |
| ≤ 13.8 kV | ≥13.8 kV , ≤22.9 kV |
2 | Designation, model | FXB-24kV/70kN | FXB-36kV/70kN | |
3 | Standards | IEC 61109:2008, ANSI C29.13 | IEC 61109:2008, ANSI C29.13 | |
4 | Manufacturing Features | |||
| Core material | Fiberglass with Fiberglas Round Rod Bar ECR | Fiberglass with Fiberglas Round Rod Bar ECR | ||
| Insulated housing and sheds: | High consistency silicone rubber type HTV or LSR | High consistency silicone rubber type HTV or LSR | ||
| - Resistance to tracking and erosion of insulating material: Silicone rubber | Class 2A, 6kV (according to ASTM D2303 – IEC 60587) | Class 2A, 6kV (according to ASTM D2303 – IEC 60587) | ||
| Material of the coupling hardware | Forged steel | Forged steel | ||
| Galvanization of hardware | According to ASTM A153/A153M, average thickness of 86µm | According to ASTM A153/A153M, average thickness of 86µm | ||
| Types of coupling | Clevis – Tongue, | Clevis – Tongue | ||
| Key | Stainless steel | Stainless steel | ||
5 | Electrical Values: | |||
| Operation voltage phase-phase | kV | 10 kV, 13.2 kV to 13.8 kV | 13.8 kV to 22.9 kV | |
| Maximum voltage for the insulator Um | kV(r.m.s) | 24 | 36 | |
| Nominal frequency | Hz | 60 | 60 | |
| Maximum diameter of the insulating part | mm | 98 | 98 | |
| Minimum creepage distance | mm | 645 | 945 | |
| Minimum arcing distance | mm | 210 | 285 | |
| Number of sheds | No. | 6 | 9 | |
| Sheds diameter | mm | 98 | 98 | |
| Passage of the sheds | mm | 35 | 35 | |
| Sheds tilt angle | ° | 3 | 3 | |
| Withstand voltage at power frequency: | ||||
| - Wet | kV | ≥100 | ≥110 | |
| - Dry | kV | ≥130 | ≥140 | |
| Impulse withstand voltage 1.2/50us: | kV | |||
| - Positive | kV | ≥190 | ≥240 | |
| Low Frequency Test Voltage (RMS to Earth) | kV | 20 | 30 | |
| RIV Maximum at 1000 KHz | µV | 10 | 10 | |
6 | Mechanical values: | |||
| Specified Maximum Mechanical Load (SML) | kN | 70 | 70 | |
| Specified Mechanical Test Load (RTL) | kN | 35 | 35 | |
| Torque | N-m | 47 | 47 | |
| Core diameter | mm | 16 | 16 | |
| Weight | kg | 1.4 | 1.9 | |
7 | Design Tests | According to clause 10 IEC 61109 | According to clause 10 IEC 61109 | |
8 | Type Tests | According to clause 11 IEC 61109 | According to clause 11 IEC 61109 | |
9 | Sampling tests | According to clause 12 IEC 61109 | According to clause 12 IEC 61109 | |
10 | Individual tests | According to clause 13 IEC 61109 | According to clause 13 IEC 61109 | |
11 | UV resistance tests | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 | According to ASTM G154 and ASTM G155 or ISO 4892-3 and ISO 16474-3 |
Product detail pictures:

Related Product Guide:
The organization keeps on the procedure concept "scientific management, high quality and efficiency primacy, purchaser supreme forOEM Famous CT/VT compartment Quotes –Suspension type Polymeric Insulator – Holley, The product will supply to all over the world, such as: Portugal, United States, UK, So far our merchandise have been exported to east Europe, the Middle East, Southeast, Africa and South America etc. We have now 13years experienced sales and purchase in Isuzu parts at home and abroad and the ownership of the modernized electronic Isuzu parts checking systems. We honor our core principal of Honesty in business, priority in service and will do our best to provide our customers with high quality items and excellent service.